|
VIKING FOAM SYSTEM SPECIFICATIONS
Download text file (FoamDeluge.zip)
FOAM DELUGE SYSTEM
The sprinkler system shall be an overhead deluge AFFF foam sprinkler system. The system shall be
designed to provide adequately proportioned foam water solution at listed water flows past the
proportioning device. The system shall be installed in accordance with NFPA 16, Standard for the
Installation of Deluge Foam-Water Sprinkler and Foam-Water Spray Systems, NFPA 11, Standard for
Low Expansion Foam, NFPA 13, Standard for Installation of Sprinkler Systems, and occupancy
standards pertaining to the system installation.
SYSTEM DEVICES
System Design
(Insert applicable system design.)
Deluge Valve
Deluge systems shall utilize a 90° pattern type of deluge valve. The deluge valve shall employ a
positive vent on the priming line to ensure that the deluge valve will not prematurely reset.
Inlet and outlet connections of the deluge valve can be flanged by flanged or flanged by grooved,
respectively. The deluge valve shall be UL listed and FM approved. The deluge valve shall have a
working pressure of 250 PSI. Valve trim shall be compatible and installed following the
manufacturer's specifications. The deluge valve manufacturer is to be The Viking Corporation, and
the Model shall be E-1.
Deluge Release System
The deluge valve shall utilize a listed and approved release system. One of the following methods
shall be incorporated in the release system:
- Deluge systems utilizing hydraulic release of the deluge valve prime water pressure
shall employ a rate-of-rise release detector, fixed temperature release, or fire
sprinkler in the release line piping. The rate-of-rise detector shall activate a
release when there is a rise of temperature of 15 °F over the period of one minute.
The rate-of-rise release shall have a means of installing a 155 °F fixed temperature
release on the device. The rate-of-rise release shall be automatically resetting.
All devices used in the hydraulic release line shall be UL listed and FM approved.
The rate-of-rise release manufacturer is to be The Viking Corporation, and the Model
shall be C-1. The fixed temperature release manufacturer is to be The Viking
Corporation, and the Model shall be M. Fire sprinklers utilized in the release line
shall be Viking Model M sprinklers.
- Deluge systems utilizing pneumatic pilot line release systems shall employ a
rate-of-rise release detector, fixed temperature release, or fire sprinkler in the
release line piping. The rate-of-rise detector shall activate a release when there
is a rise in temperature of 15 °F over the period of one minute. The rate-of-rise
release shall have a means of installing a 155 °F fixed temperature release on the
device. The rate-of-rise release shall be automatically resetting. All devices used
in the pneumatic release line shall be UL listed and FM approved. The rate-of-rise
release manufacturer is to be The Viking Corporation and the Model shall be C-1.
The fixed temperature release manufacturer is to be The Viking Corporation. The
Model shall be M. Fire sprinklers utilized in the release line shall be Viking Model
M sprinklers.
- Deluge systems utilizing electric release systems shall utilize a release control
panel and solenoid valve listed and approved for use with a Viking Deluge Valve.
Detectors shall be compatible with the release control panel. The release control
panel shall be a Viking Model B-1/Par III Release Control Panel.
Concentrate Controller (Proportioner)
The concentrate controller shall be a UL listed and FM approved device. The concentrate
controller shall be listed and approved with the foam concentrate to be proportioned and the
foam bladder tank. The concentrate controller shall be a brass wafer-type device. The
concentrate controller shall be listed with a nominal orifice plate size for the foam
concentrate to be proportioned. The concentrate controller manufacturer is to be Viking.
Foam Bladder Tank
The foam bladder tank employed in the low flow foam system shall be an ASME code pressure vessel.
The foam bladder tank utilized shall have been listed for use with the foam concentrate and
proportioning method utilized. The foam bladder tank bladder shall be constructed of Buna-N
rubber. The foam bladder tank shall adhere to the requirements set forth in NFPA 11, Standard
for Low-Expansion Foam and NFPA 16, Standard for the Installation of Deluge Foam-Water Sprinkler
Systems. The foam bladder tank shall be UL listed and FM approved. The foam bladder tank is to
be a Viking Vertical or Horizontal Foam Bladder Tank.
Concentrate Control Valve
Deluge valves that are utilized as concentrate control valves and are to be supplied by AFFF or
AR-AFFF shall utilize a 90° pattern type of deluge valve manufactured with a corrosion resistant
Halar coating. The concentrate control valve shall be externally resettable by hydraulic means.
The concentrate control valve shall employ a pressure operated relief valve (PORV) on the priming
line to release prime pressure from the top of the deluge valve. The PORV shall automatically
reset and re-prime the deluge valve once back pressure has been removed. The inlet and outlet
connections of the deluge valve can be flanged by flanged, flanged by grooved, or threaded by
threaded, respectively. The concentrate control deluge valve shall have a working pressure of
not less than 250 PSI unless listed for higher pressures. The concentrate control valve shall be
primed with an indicating control valve followed by an inline strainer, check valve, and a 1/16"
restricted orifice in line prior to the inline PORV. Concentrate control valve trim shall be
compatible and installed following the manufacturer's specifications. The Halar Coated
Concentrate Control Deluge Valve manufacturer is to be The Viking Corporation, and the Model
shall be E-2 or E-4.
Foam Concentrate Piping
Foam concentrate piping shall be compatible with foam concentrate to be used. The foam provider
shall be consulted for acceptable materials of construction. Foam concentrate piping shall be
designed for the least equivalent feet of pipe run from the bladder tank discharge outlet to
the proportioning device and water supply to the bladder tank. Excessive use of elbows and tees
shall be avoided. Foam concentrate piping shall be substantially secured and restrained against
movement, thrust, and vibration. Foam concentrate piping shall be protected from excessive heat
and freezing temperatures. Foam concentrate piping shall be installed with a fitting such as a
grooved coupling or union to be readily removed between proportioning assembly and the
concentrate control valve.
Foam Concentrate
Aqueous Film Forming Foam (AFFF) or Alcohol Resistant Aqueous Film Forming Foam (AR-AFFF) shall
be utilized. Water-soluble liquids shall be protected with Alcohol resistant type foam
concentrate. Foam concentrates shall be synthetic and stored in accordance with the
manufacturer's instructions. Foam concentrates shall be listed for use for the protection
application imposed. Foam concentrates shall be listed and approved for the discharge outlets
utilized in the protection scheme. Foam concentrates shall be listed and approved for use with
Viking's Foam Proportioning System. Foam concentrates shall be proportioned for a minimum 1% or
3% concentration in accordance with their listings. The foam concentrate shall be Viking Foam
Concentrate.
Discharge Devices
Closed head sprinklers or nozzles that have been specifically tested and found suitable for the
discharge of low expansion synthetic foam/water solution shall be installed. Standard sprinklers
or closed head nozzles used for discharge outlets shall have been tested for minimum densities
or minimum pressures as foam/water solution discharge outlets. Discharge devices shall be UL
listed or FM approved for the application for which they are used. Closed head sprinklers and
closed head nozzles shall be UL listed or FM approved for use with the foam and the flammable
liquid being protected. All sprinklers or nozzles that are to discharge foam/water solution are
to be manufactured by The Viking Corporation.
Alarm Pressure Switch
Water flow will activate an alarm by way of an alarm pressure switch. The alarm pressure switch
shall be compatible with system devices. The alarm pressure enclosure shall be UL listed and FM
approved for the application in which it is used. The alarm pressure switch shall have the
ability to be wired for Class A or Class B service. The alarm pressure switch shall be
constructed with a ½" brass pressure connection. The alarm pressure switch manufacturer shall be
The Viking Corporation, Part Number shall be 09470 or 09471.
System Overhead Piping
Overhead sprinkler piping shall be in accordance with materials deemed acceptable by NFPA 13,
Standard for the Installation of Sprinkler Systems, NFPA 16, Standard for the Installation of
Deluge Foam-Water Sprinkler Systems, and all other applicable building standards.
System Control Valve
The low flow foam system control valve shall consist of a listed indicating type of control
valve. The control valve shall be listed for use in fire protection systems. The control valve
shall be rated for system working water pressure, but in no case shall it be listed for pressure
less than 175 PSI.
Hangers and Supports
System piping shall be substantially supported from the building structure. The installation of
hangers and supports shall adhere to the requirements set forth in NFPA 13, Standard for the
Installation of Sprinkler Systems. Materials used in the installation or construction of
hangers and supports shall be listed and approved for such application. Hangers or supports not
specifically listed for service shall be designed and bear the seal of a professional engineer.
Fire Department Connection
A system fire department connection shall be provided on the system riser in accordance with
NFPA 16, Standard for Installation of Deluge Foam-Water Sprinkler Systems. The fire department
connection shall be of a brass body with an integral clapper assembly to separate flow between
inlets. The fire department connection shall be installed in an area accessible for the first
response unit; actual fire department location shall be installed and located only after proper
coordination with fire officials. The fire department connection shall be UL listed and FM
approved for fire protection use.
Underground Piping
Piping and fittings used for the installation of underground water mains shall be listed for
such service. Local water system requirements shall be adhered to. Compatible fittings and
connection methods shall be reviewed with the water department authority. The standards of the
AWWA and NFPA 24, Standard for the Installation of Private Fire Service Mains and Their
Appurtenances shall be minimum installation guidelines.
Drains and Flushing Connections
System drains shall adhere to the requirements set forth in NFPA 13, Standard for the
Installation of Sprinkler Systems. Flushing connections shall be provided where system piping
is subject to accumulation of sediments or where periodic flushing is required by the Authority
Having Jurisdiction. System auxiliary drains shall be installed so that the drain valve is
accessible and labeled as a sprinkler system drain. Drains shall terminate to the exterior of
the building where practical. Drains that do terminate to the exterior shall be installed with
a 45° elbow directed to a splash block or other permanent erosion limiting material.
Riser Test Connections
A test connection shall be provided on the system riser with a downstream isolation valve for
the purpose of testing foam proportioning. The system test header shall be of adequate size for
at least a mid-range flow of the proportioning system. The system test header shall be installed
with a means of draining any trapped sections of discharge piping subject to freezing.
System Supervision
Control valves larger than 2" in size shall be equipped with UL listed and FM approved
supervisory switches. Control valves 2" and smaller shall be sealed in the position of their
normal operating condition. Others shall execute the termination of supervisory switch wires.
Supervisory switches shall be Potter Electrical Signal Company Control Valve Supervisory Switches.
System Commissioning
The foam water sprinkler system shall be tested in accordance with NFPA 11, NFPA 13, NFPA 16,
and all other applicable codes and jurisdictions. An owner's representative, local fire
officials and a representative of the installing contractor shall witness foam-proportioning
tests. Additional foam concentrate shall be provided for testing by the installing contractor.
The installing contractor shall provide maintenance and material safety data sheets (MSDS) to
the owner.
|