|
VIKING FOAM SYSTEM SPECIFICATIONS
Download text file (WetPipeLowFlow.zip)
WET PIPE LOW FLOW FOAM SYSTEM
The sprinkler system shall be a closed head wet pipe/AFFF foam sprinkler system. The system
shall be designed to provide adequately proportioned foam water solution at low water flows past
the proportioning device. The proportioning system shall provide foam at initial fire conditions
equal to or at a greater design percentage below the minimum listed flow of the proportioning
system. The system shall be installed in accordance with NFPA 16, Standard for the Installation
of Deluge Foam-Water Sprinkler and Foam-Water Spray Systems, NFPA 13, Standard for the
Installation of Sprinkler Systems, and occupancy standards pertaining to the system installation.
SYSTEM DEVICES
System Design
(Insert applicable system design.)
Low Flow Proportioning System
The low flow proportioning system shall be totally automatic and mechanical in nature.
Electrical appliances, electric devices, electric valves, and electric pumps shall be strictly
prohibited. The proportioning system shall be of such a type that all valves, devices, foam
bladder tanks and appurtenances are of a listed and approved assembly, with foam concentrate
being supplied.
Low flow foam proportioning shall be accomplished by positive injection of foam concentrate of
a higher pressure into a lower water pressure stream passing the concentrate controller
(proportioner); the differing pressures shall be "balanced" by means of a spool valve with an
internal balanced design (ILBP).
The pressure difference (minimum 15 PSI) between the foam concentrate and the water pressure
stream passing by the proportioning device shall be created by supplying the foam bladder tank
with system supply pressure and reducing the discharge pressure of the system supply. A pilot
operated pressure control valve, listed and approved as part of the proportioning system, shall
be installed to reduce the supply pressure of the system riser.
The flow of water through the system riser shall cause the concentrate control valve to open,
allowing foam concentrate to flow into the ILBP to be balanced to the existing water flow. The
concentrate control valve shall automatically reset once the flow of water has ceased. The
concentrate control valve shall be listed as a Halar coated fire protection valve and be of a
right angle deluge valve design. Water flow in the system riser shall be directed past a listed
and approved pilot operated pressure control valve to a listed and approved alarm valve. The
alarm valve alarm port shall be utilized for water flow alarms and to release the prime pressure
of the Halar coated right angle deluge valve. Prime pressure of the Halar coated concentrate
control valve shall be released when water flow from the alarm valve alarm port back pressures
a pressure operated relief valve (PORV), venting the priming water feed and draining the priming
chamber water. Priming water pressure shall be reestablished in the priming chamber when water
flow is no longer present in the alarm valve; thereby, eliminating the flow through the
alarm port, which will allow the PORV to close and reestablish prime pressure on the Halar
coated concentrate control valve.
Pilot Operated Pressure Control Valve
Wet pipe/foam sprinkler systems shall require a reduced discharge pressure at the system riser
and shall employ the use of a listed and approved pilot operated pressure regulating valve that
has been approved with the proportioning system. The pressure regulating valve shall be factory
set and field adjustable to constant pressure regardless of inbound pressure fluctuations. The
pilot operated pressure control valve shall be listed for water working pressures of not less
than 175 PSI. The pilot operated control valve shall have, as part of its assembly: a right
angle pattern flow control valve, a pilot pressure regulating valve, a speed control assembly,
and listed galvanized trim piping assembled and tested by the manufacturer. The pilot operated
pressure control valve shall be UL listed and FM approved as an integral part of the
proportioning system. The pilot operated pressure control valve manufacturer is to be The Viking
Corporation, and the Model shall be A-2.
Foam Bladder Tank
The foam bladder tank employed in low flow foam system shall be an ASME code pressure vessel.
The foam bladder tank utilized shall have been listed for use with the foam concentrate and
proportioning method utilized. The foam bladder tank shall be compatible with Viking's Low Flow
Foam System. The foam bladder tank shall adhere to the requirements set forth in NFPA 11,
Standard for Low-Expansion Foam and NFPA 16, Standard for the Installation of Deluge Foam-Water
Sprinkler and Foam-Water Spray Systems. The foam bladder tank shall be UL listed and FM approved.
Concentrate Control Valve
Deluge valves that are utilized as concentrate control valves and are to be supplied by AFFF or
AR-AFFF shall utilize a 90° pattern type of deluge valve manufactured with a corrosive resistant
Halar coating. The concentrate control valve shall be externally resettable by hydraulic means.
The concentrate control valve shall employ a positive venting device (PORV) on the priming line
to release prime pressure from the top of the deluge valve. The PORV shall automatically reset
and reprime deluge valve once back pressure has been removed. The inlet and outlet connections
of the deluge valve can be flanged by flanged, flanged by grooved, or threaded by threaded,
respectively. The concentrate control deluge valve shall have a working pressure of not less
than 250 PSI unless listed for higher pressures. The concentrate control valve shall be primed
with an indicating control valve followed by an inline strainer, check valve, and a 1/8"
restricted orifice in line prior to the inline PORV. The concentrate control valve trim shall be
compatible and shall be installed following the manufacturer's installation instructions. The
Halar Coated Concentrate Control Deluge Valve manufacturer is to be The Viking Corporation.
The Model shall be E-2 or E-4.
Foam Concentrate Piping
Foam concentrate piping shall be compatible with foam concentrate to be used. The foam provider
shall be consulted for acceptable materials of construction. Foam concentrate piping shall be
designed for the least equivalent feet of pipe run from bladder tank discharge outlet to
proportioning device and water supply to bladder tank. Excessive use of elbows and tees shall
be avoided. Foam concentrate piping shall be substantially secured and restrained against
movement, thrust, and vibration. Foam concentrate piping shall be protected from excessive heat
and freezing temperatures. Foam concentrate piping shall be installed with a fitting such as
a grooved coupling or union to be readily removed between proportioning assembly and concentrate
control valve.
In-Line Balanced Proportioner (ILBP)
the In-Line Balanced Proportioner (ILBP) assembly shall be factory assembled and include a listed
and approved concentrate controller, brass connecting nipples, duplex gauge, braided sensing
lines, and an internally balancing designed spool valve. The ILBP shall have a working pressure
for incoming foam concentrate of 200 PSI. The spool balancing valve shall be equipped with a
copper sensing tube for the primary function of sensing flowing water pressure past the
concentrate controller and adjusting the flow of foam through internal port openings by allowing the upper
the valve disc to raise or lower the spool assembly connected to the upper valve disc. The ILBP
shall work on a minimum 15 PSI differential pressure between the higher incoming foam
concentrate and the lower flowing water pressure inlet to the concentrate controller. Braided
sensing lines shall be installed from the duplex gauge and the foam and water pressures. The
duplex gauge shall display water pressure with a needle black in color and display foam pressure
with a needle red in color. A braided sensing line for water pressure shall be installed from a
½" outlet on the system riser provided below the concentrate controller by the fire sprinkler
contractor. The ILBP shall be UL listed and FM approved as an assembly with the foam concentrate
and as an integral part of the complete system (bladder tank, pilot operated pressure control
valve, ILBP, etc). The In-line Balanced Pressure Proportioner manufacturer is to be The Viking
Corporation, and the Model shall be LFF.
Alarm Valve
The alarm valve shall be UL listed and FM approved. The alarm valve shall be equipped with a
removable cover/clapper assembly for periodic inspection of clapper and seat assembly in
accordance with NFPA 25, Standard for the Inspection, Testing, and Maintenance of Water-Based
Fire Protection Systems. The alarm valve shall be listed for installation in the vertical or
horizontal position. The alarm valve shall be equipped with gauge connections on the system side
and supply side of the valve clapper. The alarm valve shall be equipped with an external bypass
to eliminate false alarms if water flow is less than that of the flow of a single fire sprinkler.
The alarm valve trim piping shall be galvanized and be listed and approved as part of the valve
assembly. The alarm valve shall be constructed with a ductile iron body and be listed and
approved for a maximum water working pressure of 250 PSI. The alarm valve shall be equipped
with a pressure retard chamber as part of the alarm line trim. The alarm valve manufacturer is
to be The Viking Corporation, and the Model shall be J-1.
Retard Chamber
Ported alarm connections on sprinkler riser valve are to be piped to a retard chamber to absorb
variable pressure surges. The alarm pressure switch is to be installed on the retard chamber
with circuit vent trim to eliminate vapor or hydraulic lock against circuit closer. The Retard
Chamber manufacturer is to be The Viking Corporation, and the Model shall be C-1.
Foam Concentrate
Aqueous Film Forming Foam (AFFF) or Alcohol Resistant Aqueous Film Forming Foam (AR-AFFF) shall
be utilized. Water-soluble liquids shall be protected with Alcohol resistant type foam
concentrate. Foam concentrates shall be synthetic and shall be stored in accordance with the
manufacturer's instructions. Foam concentrates shall be listed for use for the protection
application imposed. Foam concentrates shall be listed and approved for the discharge outlets
utilized in the protection scheme. Foam concentrates shall be UL listed and FM approved. Foam
concentrates shall be listed and approved for use with Viking's Low Flow Foam System. Foam
concentrates shall be proportioned for a minimum 1% or 3% concentration in accordance with their
listings.
Discharge Devices
Closed head sprinklers or nozzles that have been specifically tested and found suitable for the
discharge of low expansion synthetic foam/water solution shall be installed. Standard sprinklers
or closed head nozzles used for discharge outlets shall have been tested for minimum densities
or minimum pressures as foam/water solution discharge outlets. Discharge devices shall be UL
listed or FM approved for the application for which they are used. Closed head sprinklers and
closed head nozzles shall be UL listed or FM approved for use with the foam and flammable liquid
being protected. All sprinklers or nozzles that are to discharge foam/water solution are to be
manufactured by The Viking Corporation.
Waterflow Pressure Switch
Water flow will activate an alarm by way of an alarm pressure switch. The alarm pressure switch
shall be compatible with system devices. The alarm pressure enclosure shall be UL listed and FM
approved for the application in which it is used. The alarm pressure switch shall have the
ability to be wired for Class A or Class B service. The alarm pressure switch shall be
constructed with a ½" brass pressure connection. The alarm pressure switch manufacturer shall be
The Viking Corporation, Part Number 09470 or 09471.
System Overhead Piping
Overhead sprinkler piping shall be in accordance with materials deemed acceptable by NFPA 13,
Standard for the Installation of Sprinkler Systems, NFPA 16A, Standard for the Installation of
Closed-Head Foam-Water Sprinkler Systems, and all other applicable building standards.
System Control Valve
The low flow foam system control valve shall consist of a listed indicating type of control
valve. The control valve shall be listed for use in fire protection systems. The control valve
shall be rated for system working water pressure, but in no case shall be listed for pressure
less than 175 PSI.
Hangers and Supports
System piping shall be substantially supported from the building structure. The installation of
hangers and supports shall adhere to the requirements set forth in NFPA 13, Standard for the
Installation of Sprinkler Systems. Materials used in the installation or construction of hangers
and supports shall be listed and approved for such application. Hangers or supports not
specifically listed for service shall be designed and bear the seal of a professional engineer.
Fire Department Connection
A system fire department connection shall be provided on the system riser in accordance with
NFPA 16A, Standard for the Installation of Closed-Head Foam-Water Sprinkler Systems. The fire
department connection shall be of a brass body with an integral clapper assembly to separate
flow between inlets. The fire department connection shall be installed in an area accessible for
the first response unit. The actual fire department location shall be installed and located only
after proper coordination with fire officials. The fire department connection shall be UL
listed and FM approved for fire protection use.
Underground Piping
Piping and fittings used for the installation of underground water mains shall be listed for
such service. Local water system requirements shall be adhered to. Compatible fittings and
connection methods shall be reviewed with the water department authority. The standards of the
AWWA and NFPA 24, Standard for the Installation of Private Fire Service Mains and Their
Appurtenances shall be minimum installation guidelines.
Drains and Flushing Connections
System drains shall adhere to the requirements set forth in NFPA 13, Standard for the
Installation of Sprinkler Systems. Flushing connections shall be provided where system piping
is subject to accumulation of sediments or where periodic flushing is required by the Authority
Having Jurisdiction. System auxiliary drains shall be installed so that the drain valve is
accessible and labeled as a sprinkler system drain. Drains shall terminate to the exterior of
the building where practical. Drains that do terminate to the exterior shall be installed with
a 45° elbow directed to a splash block or other permanent erosion limiting material.
Riser Test Connections
A test connection shall be provided on the system riser with a downstream isolation valve for
the purpose of testing foam proportioning. The system test header shall be of adequate size for
at least a mid-range flow of the proportioning system. The system test header shall be installed
with a means of draining any trapped sections of discharge piping subject to freezing.
System Supervision
Control valves larger than 2" in size shall be equipped with UL listed and FM approved
supervisory switches. Control valves 2" and smaller shall be sealed in the position of their
normal operating condition. Others shall execute the termination of supervisory switch wires.
Supervisory switches shall be Potter Electrical Signal Company Control Valve Supervisory Switch.
System Commissioning
The foam water sprinkler system shall be tested in accordance with NFPA 11, NFPA 13, NFPA 16,
and all other applicable codes and jurisdictions. An owner's representative, local fire
officials and a representative of the installing contractor shall witness foam-proportioning
tests. Additional foam concentrate shall be provided for testing by the installing contractor.
The installing contractor shall provide maintenance and material safety data sheets (MSDS) to
the owner.
|